Interpretation Response #PI-76-016 ([Corrosion Associates] [Richard B. Bender])
Below is the interpretation response detail and a list of regulations sections applicable to this response.
Interpretation Response Details
Response Publish Date:
Company Name: Corrosion Associates
Individual Name: Richard B. Bender
Location State: TX Country: US
View the Interpretation Document
Response text:
April 8, 1976
Mr. Richard B. Bender
  Corrosion Associates
  P.O. Box 11302
  Fort Worth, Texas 76110
Dear Mr. Bender:
In your letter of March 31, 1976, you ask whether the exemptions
  contained in Section 192.455 apply to pipelines which are subject
  to the requirements of Section 192.457. We presume the question
  arises from the wording of Section 192.457 which provides that
  certain pipelines must be cathodically protected "in accordance
  with this subpart."
By its terms, Section 192.455 specifically applies to pipelines
  installed after July 31, 1971. Likewise, Section 192.457
  specifically applies to pipelines installed before August 1, 1971.
This distinction in the scope of the two sections indicates that
  the exemptions under Section 192.455 are intended to apply only to
  pipelines installed after July 31, 1971.
In Section 192.457, the phrase "in accordance with this subpart" is
  not intended to reference the exemptions from the cathodic
  protection requirement of Section 192.455. This is particularly
  true in light of the analogous usage of the phrase in Section
  192.455 where exemptions are otherwise set forth. Rather, in both
  sections the phrase is grammatically used to describe the
  requirement for cathodic protection. The phrase indicates that
  other regulations in Subpart I, namely Section 192.463, govern the
  protection which must be provided.
Sincerely,
'signed'
Cesar DeLeon
  Acting Director
  Office of Pipeline
  Safety Operations