Referring to your letter of February 21, 1975, and figures attached thereto, the redesigned riser
shown in Figure 2 with a protective sleeve covering all plastic materials aboveground appears to
meet the requirements of 49 CFR 192.375(a) for protection of plastic service lines. Although we
do not have enough information to opine whether the riser shown in Figure 2 would meet all the
requirements of 49 CFR 192.123, we have particular misgivings about its meeting the temperature
limitations of section 192.123(b) under ordinary aboveground operating conditions.
The two 4-inch PVC lines which are shown in Figure 3 are mains. This is so because in
accordance with the definition of the term "main" in 49 CFR 192.3 each 4-inch line serves as a
common source of supply for more than one service line.
We trust this adequately responds to your inquiry.