Interpretation Response #PI-85-0102 ([PRI Gasco, Inc.] [Mr. David Y. Morikawa])

Below is the interpretation response detail and a list of regulations sections applicable to this response.

Interpretation Response Details

Response Publish Date:

Company Name: PRI Gasco, Inc.

Individual Name: Mr. David Y. Morikawa

Location State: HI Country: US

View the Interpretation Document

Response text:

Mr. David Y. Morikawa
Project Engineer
PRI Gasco, Inc.
PRI Tower 733 Bishop Street
P. O. Box 3379
Honolulu, Hawaii 96842

Dear Mr. Morikawa:

The Installation of a regulator in an alcove with a louvered door facing the outside of a building would not meet §§192.355(b)(2) or 192.357(d). Under these regulations, the vent outlet of a regulator installed inside a building must be located outside to assure that any gas escaping through the vent is released in the outside atmosphere.