Interpretation Response #PI-81-0112

Below is the interpretation response detail and a list of regulations sections applicable to this response.

Interpretation Response Details

Response Publish Date:

Company Name:

Individual Name:

Location State: PA Country: US

View the Interpretation Document

Response text:

August 18, 1981

Mr. E. L. Schmitt
Nicotine Manufacturing Corporation
1525 Liberty Avenue
Pittsburgh, PA. 15222

Dear Mr. Schmitt:

This refers to you letter of April 16, 1981, in which you requested the advice of this office on
what action you should take so that the use of malleable iron covers on you275 WOG valves will
conform to applicable standards in 49 CFR part
192. As you noted in your letter, §192.145 requires that valves meet the minimum requirements, or
the equivalent, of the industry standard, API 6A, API 6D, or MSS SP-70, all three of which require
steel covers to be used on you 275 WOG valves.

Since §192.145 permits the equivalent of the standard quoted above to be used, you may use a
malleable iron cover in complying with §192.145 if it can be demonstrated that the 275 WOG valve
constructed with a malleable iron cover would provide at least the same level of safety under
expected operating conditions as one constructed with a steel cover. You may use any qualified
expertise in making this determination, but one source, of course, would be industry groups
responsible for the quoted standards.  This office does not make equivalency determinations for
manufacturers or operators; however, Federal or State inspection personnel may judge the
correctness of any determination as part of their enforcement duties when visiting an operator’s
facilities.

To answer your question as to whether you should formally request a waiver, if equivalency is
demonstrated there is no need for a waiver since §192.145 would be satisfied. Moreover, section 3
of the Natural gas Pipeline Safety Act of 1968, as amended by Title 1 of the Pipeline Safety Act of
1979, permits the secretary of transportation to grant waivers only to persons engaged in the
transportation of gas or the operation of pipeline facilities. Since it appears that you are
engaged in the manufacturing of components for gas pipelines and not in the transportation of gas
or operation of pipeline facilities, you would not fall into the category of petitioners to whom a
waiver could be granted.

If equivalency cannot be demonstrated but there is reason to believe the 275 WOG valve can be used
safely under expected operating conditions, you may petition us to amend §192.145 to allow the use
of 275 WOG type valves with malleable iron covers in gas pipelines. Such a petition should clearly
set forth the reasons why the valve should be permitted even though it does not provide the level
of safety now required by §192.145.

Sincerely, 

Melvin A. Judah
Acting Associate Director
Pipeline safety regulation
Materials Transportation Bureau
Kerotest Manufacturing Corp
2525 Liberty Avenue
Pittsburgh, PA 15222

Regulation Sections

Section Subject
192.145 Valves