USA Banner

Official US Government Icon

Official websites use .gov
A .gov website belongs to an official government organization in the United States.

Secure Site Icon

Secure .gov websites use HTTPS
A lock ( ) or https:// means you’ve safely connected to the .gov website. Share sensitive information only on official, secure websites.

U.S. Department of Transportation U.S. Department of Transportation Icon United States Department of Transportation United States Department of Transportation

Interpretation Response #PI-76-007 ([Tennessee Public Service Commission] [John Searcy])

Below is the interpretation response detail and a list of regulations sections applicable to this response.

Interpretation Response Details

Response Publish Date:

Company Name: Tennessee Public Service Commission

Individual Name: John Searcy

Location State: TN Country: US

View the Interpretation Document

Response text:

January 30, 1976

Mr. John Searcy

Engineering Division

Tennessee Public Service Commission

Cordell Hull Building

Nashville, Tennessee 37219

Dear Mr. Searcy:

This replies to your letter of July 28, 1975, requesting interpretations for various sections of 49 CFR 192.

Question 1: Is any remedial action implied in §192.739 and §192.749? If so, would such action be subject to sections 192.195 thru 192.203 and 192.183 thru

192.189, since this would involve a change after November 12, 1970?

Reply: Sections 192.739 and 192.749 govern the maintenance of pressure limiting station relief devices and pressure regulating stations and vaults used in the transportation of gas. Remedial action as appropriate, is implicit in the requirements of these sections. Any specific component which is replaced, relocated, or changed as a result of inspections or tests made under sections 192.739 and 192.749 must comply with all applicable requirements of 49 CFR 192, including those to which you refer.

Question 2: Does the phrase "distribution system," relative to §192.741(a) and the Office of Pipeline Safety Operations' (OPSO) interpretation presented in Advisory Bulletin 74-11, apply to both high and low pressure distribution systems as defined in Part 192?

Reply: Yes.

Question 3: Define "district regulator" as used in §192.741(a).

Reply: The term "district regulator" is not used in §192.741(a). we presume you are referring to the term "district pressure regulating station," which serves as a controlled source of gas supply to a district, or area, within a gas distribution system.

Question 4: Does §192.741(a) mean that systems which are each served individually by one regulator, such as distribution systems 1, 2, and 3 as identified in Diagram A, would require telemetering or recording devices or that such recording devices would only be required on systems served by more than one regulator, such as distribution system 4 identified on Diagram A?

Reply: Section 192.741(a) is not applicable to distribution systems served by only one district pressure regulating station, as is the case for distribution systems 1, 2, and 3 in Diagram A.

However, telemetering or recording pressure gauges may be necessary for compliance with §192.741(b), which applies to a distribution system supplied by a single district pressure regulating station. As indicated by our letter to you, dated November 6, 1974, §192.741(a) only applies where two or more district pressure regulating stations supply a distribution system which is common to all such sources of supply, such as distribution system 4 in Diagram A.

Question 5: You ask us to indicate on two diagrams (A and B) where telemetering or recording devices would be required. Diagram A shows three district, labeled 1, 2, and 3, each supplied by only one district pressure regulating station, and two district pressure regulating stations supplying a distribution system, labeled 4, which is integrally interconnected downstream from the two district pressure regulating stations. In distribution system 4, both stations are located on the same side of the geometric perimeter of the distribution system.

Diagram B has essentially the same configuration as A, except that districts 1 and 4 have been combined so that the resulting integrated system is supplied by two district pressure regulating stations - one at a geometrically opposite extremity from the other.

Reply: In accordance with §192.741(a), telemetering or recording gauges are required for distribution system 4 of Diagram A and distribution system 1/4 of Diagram B. Systems 1, 2, and 3 of Diagram A and 2 and 3 of Diagram B are supplied by single district pressure regulating stations and may need telemetering or recording gauges in accordance with the criteria of §192.741(b).

Sincerely,

Cesar DeLeon

Acting Director

Office of Pipeline

Safety Operations

Regulation Sections

Section Subject
192.457 External corrosion control: Buried or submerged pipelines installed before August 1, 1971
192.739 Pressure limiting and regulating stations: Inspection and testing