USA Banner

Official US Government Icon

Official websites use .gov
A .gov website belongs to an official government organization in the United States.

Secure Site Icon

Secure .gov websites use HTTPS
A lock ( ) or https:// means you’ve safely connected to the .gov website. Share sensitive information only on official, secure websites.

Portions of the Department of Transportation are currently in shutdown/furlough status due to a lapse in appropriations. Please continue to monitor this page for updates on DOT’s operating status.

U.S. Department of Transportation U.S. Department of Transportation Icon United States Department of Transportation United States Department of Transportation

Interpretation Response #PI-73-004 ([Cathodic Protection Service] [E. P. Doremus, P. E])

Below is the interpretation response detail and a list of regulations sections applicable to this response.

Interpretation Response Details

Response Publish Date:

Company Name: Cathodic Protection Service

Individual Name: E. P. Doremus, P. E

Location State: TX Country: US

View the Interpretation Document

Response text:

Mr. E. P. Doremus, P. E.
Service Division
Cathodic Protection Service
P. O. Box 66387
Houston, Texas 77006

Dear Mr. Doremus:

Thank you for your letter of November 2, 1972, in which you forwarded information and
comments concerning the two-electrode surface potential survey method for locating areas of
active corrosion. Your comments were made with reference to an interpretation contained in the
OPS Advisory Bulletin 72-8 of August 1972 in which it was stated that OPS does not feel that the
"leap-frogging" survey method will provide any useful information in determining where active
corrosion is taking place on Dresser-coupled pipelines (insulated joints). The Bulletin went on to
say that there are other types of electrical equipment that will do this job.

Your letter suggests that the "leap-frogging" technique is no longer in use and that, therefore, it
may not be appropriate to refer to it. However, the interpretation quoted in the Bulletin was in
response to a specific question, and, as indicated "leap-frogging" is not useful for Dresser-coupled
pipelines with insulated joints. On the other hand, the "leap-frogging" surface potential survey
method is being successfully used for locating areas of active corrosion on electrically continuous
pipelines. As your letter recognizes, the purpose of "leap-frogging" is to compensate for
electrode potential differences. While we recognize that there is equipment available today which
makes it unnecessary to use "leap-frogging," the leap-frogging technique remains available for use
on electrically continuous pipelines.

Your letter also states that the two-electrode surface potential survey method is the most
satisfactory approach for providing Dresser-coupled pipelines with adequate cathodic protection.
To the extent that you are referring to the use of two electrodes in continuous contact with the
earth, we agree. The proper technique provides for a continuous voltage difference measured
between one electrode placed over the pipeline and the other electrode located five feet from the
pipeline and perpendicular to the pipeline. The survey is normally conducted on both sides of the
pipeline to identify existing galvanic anodes.

Your interest in this important aspect of pipeline safety is appreciated. If you have further
questions, or comments, please contact us.