Interpretation Response #PI-87-002


Below is the interpretation response detail and a list of regulations sections applicable to this response.

Interpretation Response Details

Response Publish Date: 08-10-1987
Company Name: Public Utilities Commission    Individual Name: Robert S. Stone
Location state: OH    Country: US

View the Interpretation Document


Response text:

Mr. Robert S. Stone, P.E.
Chief, Gas Pipeline Safety
State of Ohio
Public Utilities Commission
180 East Broad Street
Columbus, Ohio 4366-0573

Dear Mr. Stone:

I apologize for the delay in answering your April 1 letter regarding the application of 49 CFR 192.199(g) to an East Ohio Gas Company vault.

We have examined the photographs and drawings of the vault, and believe that unless the installation is "grandfathered" or additional overpressure protection is provided elsewhere, it is violation of 49 CFR 192.199(g). The violation would be due to insufficient separation between the district regulator and the other regulators or the lack of any other means of protection, such as a barrier to prevent a potential explosion in the vault from damaging all the regulators.

Sincerely,

/signed/

Richard L. Beam
Director
Office of Pipeline Safety


Regulation Sections

Section Subject
§ 192.199 Requirements for design of pressure relief and limiting devices