Interpretation Response #PI-83-0100
Below is the interpretation response detail and a list of regulations sections applicable to this response.
Interpretation Response Details
Jan 10, 1983
Mr. Kenneth J. Dooley District Sales Manager Ameron
Corrosion Resistant Piping Division
596 West Lambert Road
Brea, California 92621
Dear Mr. Dooley:
This refers to your letter of November 30, 1982, requesting our approval of Ameron RTR pipe for use
in pipelines that are subject to 49 CFR Part 195.
The Part 195 safety standards for hazardous liquid pipelines do not prohibit the use of pipe made
of materials other than steel. Thus, a special approval or waiver is not required for the use of
such materials. However, as more fully stated in §195.8, the use of any material other than steel
in a proposed pipeline is conditioned upon the operator of the proposed pipeline giving prior
notice to this agency so that a determination can be made about the safety of the pipeline before
transportation begins. A separate notice must be given for each pipeline that is to be constructed
of a material other than steel.
The letter you have sent to us does not meet the notice requirements of §195.8; thus, we will not
begin any action under that section until proper notice is received from the operator.
Sincerely,
Original signed by
Richard L. Beam
Associate Director for
Pipeline Safety Regulation
Materials Transportation Bureau
Ameron
595 West Lambert Road
Post Office Box 1010
Brea, California 92621
November 30, 1982
Mr. Richard Beam
Associate Director
Office of Pipeline Safety Regulations
Material Transportation Bureau
400 - 7th St. S.W.
Washington, D.C. 20590
Dear Mr. Beam:
Long Beach Oil Developers, Long Beach, California
Pipeline Safety Regulations - Hazardous Liquids, Section 195
The above subject covers the transporting of oily water. The water content as I understand it, is
in excess of
95% and less than 5% oil.
The Long Beach Oil Developers are contemplating the replacement of steel mortar lined pipe because
of continuing corrosion in the lines with resultant leaks. In addition to the corrosive leaks,
there is a combination of corrosion and erosion causing a build up on the inside diameter and
eventual clogging of the line.
I am enclosing literature on the Ameron Bondstrande® RTR Pipe which will be corrosion free on both
the inside and outside diameter. Being corrosion free, you will have a product that will not leak
or clog due to the effects of corrosion and erosion.
I am also attaching copies of:
A) Mil Spec P-22245A - Condensate and Jet Fuel
B) Mil Spec P-28584 - Condensate
C) Jet Fuel Case Histories
D) U.S. Government Users List
The conditions of the pipe line are 160°F with a 200 psi working pressure. We would furnish a 14
Bar (205 psi) piping system with a 4 to 1 safety factor. The pipe is buried in 3 to 4 feet of earth
cover and is extremely strong and resistant to external loading. I am attaching a picture on 12"
pipe where we have subjected the pipe to a tractor running over it.
I would appreciate your approval for Ameron RTR pipe in this type of service by your permitting a
waiver at this time and eventually granting permission. It is a definite advantage over the steel
pipe.
I thank you for your help and cooperation. Very truly yours,
Kenneth J. Dool
District Sales Manager
1 . SCOPE
MILITARY SPECIFICATION PIPE AND PIPE FITTINGS
GLASS FIBER REINFORCED PLASTIC
MIL-P-22245A (DOCKS)
12 March 1963
Superseding
MIL-P-22245 (DOCKS)
13 November 1961
1.1 Scope. This specification covers pipe and fittings made from epoxy resin and glass fiber
reinforcement for the transport of liquid materials, together with epoxy adhesives necessary for
joint assembly.
1.2 Classification. The reinforced plastic pipe and fittings shall be of the following types and
classes, as specified (see 6.2).
Type I - 150 degrees F.
Class A - 150 psi
Class B - 500 psi
Type II - 200 degrees F.
Class A - 150 psi
Class B - 500 psi
Type III - 300 degrees F.
Class A - 150 psi
Class B - 500 psi
2 . APPLICABLE DOCUMENTS
2.1 The following specifications and standards, of the issue in effect on date of invitation for
bids, form a part of this specification to the extent specified herein.
SPECIFICATIONS FEDERAL
PPP-B-601 - Boxes, Wood, Cleated-Plywood.
PPP-B-621 - Boxes, Wood, Nailed and Lock-Corner. MILITARY
MIL-C-132- Crates, Wood, Open; Maximum Capacity 2,500 Pounds.
STANDARDS FEDERAL
FED. TEST METHOD STD. NO. 406 - Plastics: Methods of Testing.
MILITARY
MIL-STD-105 - Sampling Procedures and Tables for Inspection by Attributes. MIL-STD-129 - Marking
for Shipment and Storage.
(Copies of specifications and standards required by contractors in connection with specific
procurement functions should be obtained from the procuring activity or as directed by the
contracting officer.)
2.2 Other publications. The following documents form a part of this specification to the extent
specified herein. Unless otherwise indicated, the issue in effect on date of invitation for bids
shall apply.
NATIONAL BUREAU OF STANDARDS
Handbook H28 - Screw-Thread Standards for Federal Services.
(Application for copies should be addressed to the Superintendent of Documents, Government Printing
Office, Washington 25, D.C.)
AMERICAN SOCIETY FOR TESTING AND MATERIALS
D1694-59T - Threads for Reinforced Thermosetting Plastic Pipe.
(Copies may be obtained from the American Society for Testing and Materials, 1916 Race Street,
Philadelphia 3, Pennsylvania.)
3. REQUIREMENTS
3.1 General. All. plastic pipe and fittings shall be round and straight, of uniform quality and
workmanship, and free from all defects including indentations, delaminations, bends, cracks,
bubbles, pinholes, porosity, resin rich areas, and resin starved areas which due to their nature,
degree, or extent, detrimentally affect the strength and serviceability of the pipe and fittings.
Pipe lengths shall have uniform lineal density, resin content, and surface finish throughout the
length of the pipe. All pipe ends shall be cut at right angles to the axis of the pipe and any
sharp edges removed. The bore of the pipe shall contain a smooth, uniform liner to protect the
glass fiber reinforcement. The liner shall be composed of an epoxy resin formulation and may
contain a non-glass fiber reinforcement. The bore of the fittings shall have a smooth, uniform
surface with no exposed fibers. Type I pipe and fittings shall be suitable for service up to 150
degrees F., Type II pipe and fittings for service up to 200 degrees F., and Type III pipe and
fittings for service up to 300 degrees F. Class A pipe and fittings shall be suitable for service
up to 150 psi and Class B pipe and fittings for service up to 500 psi. The use of "psi" throughout
this specification shall be construed as meaning gauge pressure.
3.2 Preproduction qualification. The plastic pipe and fittings furnished under this specification
shall be a product which has been tested and has passed the qualification inspection (examination
and tests) specified herein. Awards will be made only for such products as have, prior to the time
set for opening of bids, been tested and approved. Each manufacturer who desires to qualify plastic
pipe and fittings under this
specification shall have met the production experience requirements and shall furnish the
personnel, facilities, and other data required prior to requesting qualification. Approval of the
preproduction sample by the activity concerned shall not relieve the contractor of his obligation
to supply pipe and fittings conforming to this specification. No changes or deviations from the
preproduction sample will be acceptable without prior
written approval from the Bureau of Yards and Docks.
3.2.1 Production experience. The manufacturer, at the time of request for qualification, shall have
at least 6 months production experience in making plastic pipe or fittings of the type, class,
size, process, and reinforcement for which qualification is desired. Production, as used in this
specification is defined as the repetitive manufacture of glass fiber reinforced plastic laminated
parts of the same design in accordance with a standard specification. A standard specification is
the written document employed by the manufacturer listing details of manufacture of the plastic
item and the performance required thereof.
3.2.2 Qualification procedure. The manufacturer shall request the Department of the Navy, Bureau of
Yards and Docks, Washington 25, D. C., for authorization to conduct qualification inspection under
the supervision of a Government inspector at the manufacturer's own laboratory or other laboratory
satisfactory to the Bureau of Yards and Docks, with the cost of such inspection to be borne by the
manufacturer. The request shall include three copies of the following information:
(a) A list showing the number of engineers, technicians, leadmen, and administrative personnel with
the number of years of glass fiber reinforced plastic experience of each one; the size, quantity,
and length of time in production of each unit proposed for qualification; and a complete list and
description of all production and quality control facilities and equipment including a description
of all fabricating processes, procedures, and equipment used.
(b) Types, classes, and sizes of pipe and fittings, and type of thread for which qualification is
desired (see 1.2, 3.7, and 3.8), together with a list of all materials used in the fabrication
including the number or brand designation of glass fiber reinforcement, resin, and curing agent,
and the type of treatment or finish on the glass fibers and chemical name of the curing agent.
3.2.2.1 Authorization. Upon review of the information, the Bureau of Yards and Docks will advise
the manufacturer concerning authorization to conduct qualification inspection. When authorization
has been given, the manufacturer shall, upon completion of all qualification inspection
requirements, submit to the Bureau of Yards and Docks, through the Government inspector, reports of
the results of all examinations and tests including a complete description of adhesives used in
making the joint tests. The report shall also include the information required under qualification
tests which require testing to failure of the sample. In addition, the manufacturer shall forward
to the Bureau of Yards and Docks for retention a sample of the pipe or fittings identical to those
used for the qualification inspection. The pipe sample forwarded shall be 18 inches in length. Upon
review of the inspection reports, the Bureau of Yards and Docks will advise the manufacturer of the
qualification status of his products.
3.2.3 Qualification combinations. Each specific type, class, and size of pipe and fitting, and when
applicable, type of thread shall pass the qualification inspection requirements in order to be
qualified for that particular combination, except as limited by the provisions stated in 4.3.
3.2.4 Qualification sample. Sample pipe and fittings required for preproduction qualification
inspection shall be fittings or pieces of pipe selected at random by the Government inspector out
of normal production. Pipe shall be a minimum length of 15 feet.
3.2.5 Qualification tests. Samples must pass all qualification tests. If any sample fails a
qualification test, an additional three samples shall be tested. Failure of any of the additional
samples to pass the test shall reject from qualification the specific pipe or fitting represented
by the sample. Requests for qualification of products which have previously failed to pass the
tests shall be accepted only after it has been shown to the satisfaction of the Bureau of Yards and
Docks that changes have been made to correct the deficiencies.
3.3 Material. Material shall be as specified herein. Material not definitely specified shall be of
the quality regularly used by the manufacturer in the product he sells on the commercial market.
All material
shall be new and unused and shall be free from all deleterious defects and imperfections.
3.4 Standard product. Except where modified herein, it is intended that the product and its
component parts shall be a regular commercial product of the manufacturer or his suppliers.
3.5 Design. The design of the pipe and fittings shall be in accordance with the best engineering
practice. The pipe, fittings, and adhesives shall permit assembly, maintenance, and servicing in
the field. The design shall be such as to prevent conditions which may be hazardous to personnel or
deleterious to associated environments.
3.6 Potable service. To be acceptable for potable service, the pipe, fittings, and adhesives shall
be non- toxic as evidenced by the data required in 4.3.2.1 (see 6.2).
3.7 Dimensions.
3.7.1 Pipe. Dimensions of pipe shall be in accordance with Table I (see 6.2). All pipe of the same
Type, Class, size and manufacturer shall have the same wall thickness subject to the O.D. tolerance
limits of Table I.
Table I Dimensions of Pipe
Nominal Outside Diameter,
O.D. Tolerance,
Pipe Size, Inches Inches
Inches
2 2.375
± 0.012
2-1/2 2.875
.012
3 3.500
0.12
3-1/2 4.000
0.12
4 4.500
0.15
5 5.563
0.15
6 6.625
0.25
8 8.625
0.25
10 10.750
0.25
12 12.750
0.25
3.7.1.1 The length of the pipe shall be from 15 to 22 feet unless otherwise specified (see 6.2).
3.7.2 Fittings. Fittings shall be of the same nominal sizes indicated in Table 1(see 6.2).
3.8 Threads. Thread connections shall be 60 degree stub threads conforming to ASTM Designation
D1694-591 or shall be iron pipe threads conforming to the National Bureau of Standards Handbook
H28, as specified (see 6.2).
3.9 Resins.
3.9.1 Laminating resins shall be thermosetting epoxy resins of commercial first quality.
3.9.2 Adhesives for joint assembly shall be epoxy resin base materials. When specified (see 6.2) a
sufficient quantity of adhesive shall be provided for joint assembly, and shall be the same
adhesive used by the manufacturer in the qualification of his product. Instructions for use shall
be marked on the container.
3.10 Glass fiber reinforcement used in the manufacture of the pipe and fittings shall be glass of
commercial first quality.
3.11 Beam deflection. The calculated value of E shall be a minimum of 1,000,000 when tested in
accordance with 4.3.2.2. The manufacturer shall recommend the spacings of hangers such that a
concentrated load in midspan of the hangers in an installation produces deflections not exceeding
0.1 inch and 0.5 inch at the test temperature. The concentrated loads used to determine the hanger
spacing shall be in accordance with the average pipe insulation weights shown in Table II.
Table II Insulation Weights
Nominal Pipe
Insulation Weights, Size, Inches
Pounds per Linear Foot
2
1.5
2 ½
2.0
3
2.0
3 ½
2.5
4
2.5
5
3.0
6
3.5
8
5.0
10
6.0
12
7.0
3.12 Expansion and creep. When tested in accordance with 4.3.2.3 and 4.3.2.3.1, the circumferential
expansion and creep shall be not greater than 0.3 percent, the axial expansion and creep shall be
not greater than 0.2 percent, and there shall be no porosity, distortion, or structural failure of
the pipe and fittings. All recorded readings shall be submitted to the Bureau of Yards and Docks.
3.13 Cycling. Pipe and fittings shall show no porosity or structural failure when tested in
accordance with
4.3.2.4.
3.14 Impact resistance. Pipe and fittings shall show no porosity when tested in accordance with
4.3.2.5.1 and 4.3.2.5.2.
3.15 Delamination resistance. Pipe shall show no evidence of delamination or porosity when tested
in accordance with 43.2.6.
3.16 Boil resistance. Samples of Type III pipe and fittings shall show no evidence of delamination
or other impairment and shall have a weight gain no greater than 1.0% when tested in accordance
with 4.3.2.7.
3.17 Joint strength. Bonded or threaded joints and pipe and coupling shall show no porosity or
other evidence of failure after 168 hours when tested in accordance with 4.3.2.8. In addition a
report of the type of failure and pressure at which failure occurs in the short-time burst test
shall be submitted to the Bureau of Yards and Docks.
3.18 Short-time burst. After testing the pipe in accordance with 4.3.2.9, a report of the results
shall be submitted to the Bureau of Yards and Docks.
3.19 Specific gravity. When tested in accordance with 4.3.2.10, the specific gravity of
preproduction sample pipe and fittings shall be within the range of plus or minus 5 percent of the
average of the five preproduction samples. The specific gravity of production samples shall not
vary more than plus or minus 5 percent from the average of the preproduction results.
3.20 Resin content. When tested in accordance with 4.3.2.11, the resin content of preproduction
sample pipe and fittings shall be within the range of plus or minus 5 percent of the average of the
five preproduction samples. The specific gravity of production samples shall not vary more than
plus or minus 5
percent from the average of the preproduction results.
3.21 Hardness. When tested in accordance with 4.3.2.12, the Rockwell hardness number for the
preproduction sample pipe and fittings shall be within the range of plus or minus 5 percent of the
average
for the five preproduction samples. The Rockwell hardness number for the production samples shall
not vary more than plus or minus 5 percent from the average of the preproduction results.
3.22 Burning rate. The burning rate of the pipe shall not exceed 0.5 inch per minute when tested in
accordance with 4.3.2.13.
3.23 Hydrostatic proof test. Pipe and fittings shall withstand 1-1/2 times the psi for the top
bracket of its class without any indication of porosity when tested in accordance with 4.4.5.1.1.
3.24 Identification marking. Each pipe shall have permanent identification marking at intervals no
more than 3 feet apart between markings along the length of the pipe. Each length of pipe and each
fitting shall be marked and identified as follows:
1. Specification number.
2. Type and Class.
3. Pressure rating (degrees F. and psi).
4. Manufacturer's name.
5. Date of manufacture.
6. Suitable for potable service (when applicable).
3.25 Quality control facilities. The manufacturer shall have the necessary quality control
facilities and equipment by which the quality of raw materials and end use products can be
determined and controlled.
4. QUALITY ASSURANCE PROVISIONS
4.1 Unless otherwise specified in the contract or purchase order, the supplier is responsible for
the performance of all inspection requirements as specified herein. Ekcept as otherwise specified,
the supplier may utilize his own facilities or any commercial laboratory acceptable to the
Government. The Government reserves the right to perform any of the inspections set forth in the
specification where such inspections are deemed necessary to assure supplies and services conform
to prescribed requirements.
4.2 Inspection. Inspection (examination and tests) shall consist of the following:
a. Preproduction qualification inspection.
b. Production inspection.
4.3 Preproduction qualification inspection. Preproduction qualification inspection shall consist of
all the examinations specified in 4.3.1 and all the tests specified in 4.3.2. When two or more
sizes of the same type and class of pipe and fittings are offered for preproduction qualification
inspection, the expansion and creep, cycling, delamination resistance, boil resistance, and burning
rate tests specified in 4.3.2.3, 4.3.2.4,
4.3.2.6, 4.3.2.7, and 4.3.2.13 shall be performed on only one size. Selection of the size for these
tests shall be made by the Bureau of Yards and Docks.
4.3.1 Examination. The sample pipe and fittings shall be examined for the following defects:
Incorrect dimensions, threads not in accordance with requirements, out of roundness, lengths not
straight, indentations, delaminations, bends, cracks, bubbles, pinholes, porosity, resin rich
areas, resin starved areas, pipe not cut at right angles and sharp edges not removed, inside
surfaces not smooth and uniform, and
identification marking incorrect or missing.
4.3.1.1 Dimensions. Compliance with dimensional requirements shall be determined by the following
methods of measuring.
4.3.1.1.1 Wall thickness. The wall thickness shall be measured with a spring-loaded dial caliper or
screw micrometer equipped with an inner anvil with a radius substantially smaller than the radius
of the inside of the pipe. Four measurements shall be made at the open end of each sample and four
measurements on each of six sections cut
along its length to show consistency of wall thickness throughout the length.
4.3.1.1.2 Outside diameter. The outside diameter shall be measured with a flat anvil micrometer or
vernier caliper capable of reading in 0.001 inch increments. The same number of measurements as
required for the wall thickness measurements shall be made using the same wall thickness samples.
4.3.1.1.3 Out-of-roundness. The out-of-roundness shall be determined by the fit of a "go-no go"
gage.
4.3.1.1.4 Other dimensions. Dimensions other than those above shall be measured in accordance with
standard practices.
4.3.2 Tests. Tests which are specified at "roan temperature" are to be accomplished under normal
roam conditions with the temperature not to be below 65 degrees F. This will allow testing to be
done in areas which do not have close roam temperature control. Tests shall not be accomplished in
areas of abnormally high or low humidities.
4.3.2.1 Potable service data. To qualify pipe, fittings, and adhesives for potable service, the
manufacturer shall submit to the Bureau of Yards and Docks for approval all pertinent data
supporting potable service acceptability, including extraction study details and results, and a
list of the materials, with their chemical and trade names, used in the manufacturing process.
4.3.2.2 Beam deflection. A minimum 6 foot length of pipe shall be capped and filled completely with
water but not pressurized. The pipe shall be suspended by laying the end caps on appropriate
supports, allowing the pipe to hang free between the supports, and supporting the end caps at their
centers of gravity. Type I and Type II pipe shall be tested with water at 120 degrees F. Type III
pipe shall be tested with water at 200 degrees F. The sag in the pipe shall be measured and
recorded every 168 hours for a period of
1008 hours plus or minus 8 hours. The sag at. the end of the test shall be used to calculate the
value of E in the formula:
Y = 22.5 W L4
El
Where I = p (D4 – D14).
64
W = weight per foot of pipe, including water Sag is measured
from the
L = Length of span, feet
horizontal plane of the
Y = deflection or sag, inches
pipe supports to the D = outside diameter of pie, inches
lower surface of the D1 = inside diameter of pipe, inches
loaded pipe
4.3.2.3 Expansion and creep. A minimum 6 foot length of pipe shall be capped or plugged and filled
completely with fresh water containing a soluble fluorescent dye. The pipe shall be laid on lightly
greased, 1/2 inch wide steel bars spaced every 2 feet, with the top of the bars on one horizontal,
plane. The ends of the pipe shall be unrestrained. The pipe shall be equipped with gages for
measuring circumferential and axial expansion and creep of the pipe. Micrometer gages, strain gages
(SR-4 type), or equivalent extensometer having an accuracy of 0.000] inch shall be applied in three
locations. Two of these gages shall be mounted so as to indicate circumferential expansion, the
other to indicate axial expansion. The circumference and length of the pipe shall be recorded
before, during, and after pressurization. Hydrostatic pressure at 1-1/2 times the psi for the top
bracket of its class shall be maintained at room temperature for a minim= of 2000 hours. Readings
shall be recorded to the nearest 0.001 inch. Sufficient readings (maximum 96 hour intervals) shall
be taken during the test to provide a significant data plot. At the end of the 2000 hour period,
while the sample
is still under pressure, it shall be examined for porosity, distortion, and structural failure. In
this and other tests where examination for porosity is made, the detection of small amounts of
weeping shall be accomplished by viewing the samples in a darkened area with a suitable
ultra-violet lamp such that a droplet of water containing the fluorescent dye will glow brightly
and be easily detectable. After completion of the examinations, the pressure shall be released and
readings recorded until they show no further change in pipe dimensions.
4.3.2.3.1 The above procedure shall be repeated on separate samples with the internal water
temperature at 150 degrees F for Type II and Type III pipes and at 1-1/2 times the psi pressure for
the top bracket of its class.
4.3.2.4 Cycling. At the termination of the expansion and creep test (4.3.2.3 and 4.3.2.3.1), the
samples shall be held at room temperature and cycled between 0 and 1-1/2 times the psi for the top
bracket of its class for 10,000 cycles. Approximately 7 seconds time shall be used to amply the
pressure followed by a 30 second dwell at full pressure, and then immediate removal of the pressure
followed by 30 second dwell at zero pressure. At the end of this cycling test, the samples shall be
allowed to remain pressurized at 1-1/2 times the psi for the top bracket of its class for 2 hours,
at the end of which time the samples shall be examined for porosity with an ultra-violet lamp and
for structural failure.
4.3.2.5 Impact resistance.
4.3.2.5.1 Pipe. A steel ball 2 inches in diameter and weighing approximately 1-1/4 pounds shall be
dropped squarely onto the surface of the pipe with a free fall (which may be guided) for a distance
of 1 foot. The ball may be caught or deflected after the hit so that the rebound does not hit the
pipe. The pipe shall be full of water containing a soluble fluorescent dye but not pressurized. The
test shall be made at room temperature and the pipe shall be supported on its bottom axis on a
solid flat support. Four drops shall be made on randomly selected areas which are a minimum of 12
inches and 90 degrees clockwise from each other. The test shall be repeated on the same pipe but
with the pipe pressurized at the maximum service pressure. Four drops shall be made on different
areas from those previously used. The pipe shall then be pressurized to 1-1/2 times the psi for the
top bracket of its class and shall remain at this pressure for 168 hours at the end of which time
the pipe shall be examined for porosity with an ultraviolet lamp.
4.3.2.5.2 Fittings. Fittings shall be tested following the above procedure except that the drops
shall be reduced from four to one in each test.
4.3.2.6 Delamination resistance. A 2-1/2 inch long sample shall be cut at least 4 inches from the
end of a length of pipe and tested in the fixture shown in Figure 1. The sample shall be tested at
room temperature Under 500 psi hydrostatic pressure for 168 hours. No oil or other foreign material
shall be on the sample or
in the water. At the end of the test period, the sample shall be examined for indications of
delamination or porosity (through outside wall, inside wall, or the non-exposed edge).
4.3.2.7 Boil resistance. Three test samples, 1-1/2 inches in length, shall be cut from a length of
Type Ill pipe. The samples shall be taken from sections at least 6 feet apart along the length of
the pipe. Type III fittings shall be tested using either the whole fitting as the test sample or
three 1-1/2 inch lengths cut from the fitting. The samples shall be conditioned for 8 hours at 300
degrees F., desiccated, and an initial weighing made. The samples shall then be suspended in a
boiling distilled water bath for 3 hours. The samples shall then be removed one at a time, blotted
dry of excess water, and weighed. This weighing shall be made
within 1 ± 0.5 minute after removal from the bath. After weighing, the samples shall be visually
examined for delamination or other evidence of impairment and the percentage weight gain of the
samples shall be calculated as follows:
% weight gain = B —A X 100
A
Where A = initial weight
B = weight after immersion
43.2.8 Joint strength. Two pieces of pipe shall be cut so that when they are joined together with a
compatible coupling, the overall length shall be 18 inches or 7 times the outside diameter,
whichever is greater. The pipe shall be cut so that the coupling is within 1 inch of the center of
the completed test section. Unthreaded joint assemblies shall be made with an adhesive as
recommended by the manufacturer and shall be applied and cured as under field conditions in
accordance with his printed instructions. The test section shall be subjected to a hydrostatic
pressure of 1-1/2 times the psi for the top bracket of its class for 168 hours at 150 degrees F.
for Type I, 200 degrees F. for Type II, and 300 degrees F. for Type Ill pipe and coupling. The
liquid medium shall contain a soluble fluorescent dye and may be oil or water. Observations shall
be made each 24 hours for porosity (using an ultra-violet lamp) or other evidence of failure of the
pipe, coupling, or joint. If the test section is not defective at the conclusion of the 168 hours,
it shall be tested to failure by subjecting it to the short-time burst test (43.2.9) at the maximum
service temperature for the Type. The test report shall include the time to failure, type of
failure, and the psi at which failure occurs.
4.3.2.9 Short-time burst. Three samples shall be cut from a length of pipe. The length of each
sample shall be 18 inches or 7 times the outside diameter, whichever is the greater. The test shall
be made using an appropriate sealing plug in each end which are restrained by a holding frame or
rod so that loading is pat on the pipe. The pipe sample shall be pressurized at an approximate rate
of 1000 psig per minute. If the pipe circumference expands beyond the capacity of the sealing
mechanism to hold pressure, collett-like holding bands may be used over the outside of the pipe
over the sealing area to prevent excessive expansion. The pipe failures must occur away from these
bands and in the central area of the pipe to be valid. The test shall be run at roan temperature,
and the sample shall be tested to failure. A failure is defined as porosity, horizontal
splits, delaminations, bursts, or other defects which permit the transmission of the test fluid to
the outside
surface of the pipe. The test report shall include the time to failure, type and location of
failure, and the psig at which failure occurs for each of the three samples.
43.2.10 Specific gravity. Five samples selected from various sections of the pipe or fitting shall
be tested in accordance with Method 5011 of Federal Test Method Standard No. 406.
4.3.2.11 Resin content. Five samples selected from various sections of the pipe or fitting shall be
tested in accordance with Method T061 of Federal Test Method Standard No. 406.
4.3.2.12 Hardness. The hardness of pipe and fittings shall be determined with a Rockwell Hardness
Tester in accordance with Method 1081 of Federal Test Method Standard No. 406. A V-notch anvil
shall be used for cylindrical specimens.
4.3.2.13 Burning rate. The burning rate of the pipe shall be determined in accordance with Method
2021
of Federal Test Method Standard No. 406.
4.4 Production inspection. Production inspection shall be performed as part of the manufacturer's
production quality control procedure and shall include the following inspection.
4.4.1 Lot.
4.4.1.1 Pipe. All pipe of the same Type, Class, and size produced in any one 24 hour period and to
be offered for delivery under a contract or order shall be considered a lot for purposes of
inspection.
4.4.1.2 Fittings. All fittings of the same Type, Class, and size produced in any one 24 hour period
and to be offered for delivery under a contract or order shall be considered a lot for purposes of
inspection.
4.4.2 Sampling for examination. A random sample of pipe and fittings shall be selected from each
lot in accordance with Standard MIL-STD-105, using an AQL of 4.0 percent defective.
4.4.3 Sampling for tests (except hydrostatic proof test for pipe).
4.4.3.1 Pipe. A random sample of pipe shall be selected from each lot in accordance with Standard
MIL- STD-105 using inspection level L-4, and an AQL of 4.0 percent defective.
4.4.3.2 Fittings. A random sample of fittings shall be selected from each lot in accordance with
Standard
MIL-STD-105 using, inspection level L-4, and an AQL of 6.5 percent defective.
4.4.4 Examination. Sample pipe and fittings selected in accordance with 4.4.2 shall be examined as
specified in 4.3.1. Any sample pipe or fitting having one or more of the defects listed shall be
considered a defective unit.
4.43 Tests.
4.4.5.1 Pipe. Each length of pipe to be furnished under a contract or order shall be subjected to
the hydrostatic proof test specified in 4.4.5.1.1. Any length of pipe failing to pass the
hydrostatic proof test shall be rejected. Sample pipe selected in accordance with 4.4.3.1 shall be
subjected to the specific gravity, resin content, and hardness tests specified in 4.3.2.10,
4.3.2.11, and 4.3.2.12. Any sample failing to pass any of these tests shall be considered a
defective unit.
4.4.5.1.1 Hydrostatic proof test. The pipe shall be filled completely with fresh utter and
pressurized at 1-
1/2 times the psi for the top bracket of its class. Threaded end connectors shall be used on
threaded pipe. The test shall be made at room temperature and after the internal pressurizing water
has had time to reach the room temperature. The pipe shall remain under pressure for not less than
5 minutes and at the end of that time the pipe shall be examined for porosity.
4.4.5.2 Fittings. Sample fittings selected in accordance with 4.4.3.2 shall be subjected to the
specific gravity, resin content, and hardness tests specified in 4.3.2.10, 4.3.2.11, and 4.3.2.32.
Any sample failing to pass any of these tests shall be considered a defective unit.
4.5 Inspection of preparation for delivery. The packaging, packing, and marking of the pipe and
fittings, and adhesive when furnished, shall be examined to determine conformance with the
requirements of Section
5 of this specification.
5. PREPARATION FOR DELIVERY
5.1 Packaging. Packaging shall be level A or C, as specified (see 6.2).
5.1.1 Level A. All threaded pipe shall have the threads completely covered with thread protectors.
All non- threaded pipe shall have the open ends sealed with suitable caps or plugs.
5.1.2 Level C. The pipe and fittings shall be packaged in accordance with the suppliers standard
practice.
When adhesive is furnished it shall be packaged in the standard commercial containers and
quantities normally specified by the pipe manufacturer for this product.
5.2 Packing. Neking shall be level A, B, or C, as specified (see 6.2).
5.2.1 Level A.
5.2.1.1 Pipe. The pipe shall he packed in open wood crates conforming to Specification MIL C-132.
5.2.1.2 Fittings. The fittings shall be packed in close-fitting cleated-plywood boxes conforming to
Specification PPP-B-601 (overseas type) or nailed wood boxes conforming to Specification PPP-B-621
(class 2).
When the gross weight of a box exceeds 250 pounds, the box shall be modified by the addition of
skids in accordance with the applicable box specification.
5.2.1.3 Adhesive. Adhesive, when furnished, shall be packed as specified for fittings.
5.2.2 Level B. The pipe and fittings, and adhesive when furnished, shall be packed as specified for
level A
except that boxes shall be the domestic type or class, as applicable.
5.2.3 Level C. The pipe and fittings, and adhesive when furnished, shall be packed in a manner
which will insure arrival at destination in satisfactory condition and which will be acceptable to
the carrier at lowest
rates.
5.3 Marking. Shipping containers shall be marked in accordance with Standard MIL-STD-129.
6. NOTES
6.1 Intended use. Pipe and fittings covered by this specification are suitable for handling hot and
cold liquids, including dilute acids, and steam within the temperature and pressure limitations
specified for the particular types and classes, and for other uses if found to be suitable.
6.2 Ordering data. Procurement documents should specify the following:
( a) Title, number, and date of this specification.
( b ) Type and Class of pipe and fittings required (see 1.2).
( c) Quantity, size, and length of pipe required (see 3.7 and Table I).
( d ) Quantity and size of fittings required (see 3.7)-
( e ) Type of thread when required (see 3.8).
( f ) Whether adhesive is to be provided (see 3.9.2 and 6.3)
( g ) Whether pipe, fittings, and adhesives for potable service are required (see 3.6).
( h ) Level of packaging and level of packing required (see 5.1 and 5.2)
6.3Adhesives. When pipe and fittings are being procured for stock or will be stored for more than
one year before use, the adhesive should not be specified, since it may have a limited shelf life.
6.4 Jointing. Only pipe, fittings, and recommended adhesives from the same manufacturer should be
used together.
6.5 Qualification. With respect to products requiring qualification, awards will be made only for
such
products as have, prior to the time set for opening of bids, been tested and approved for inclusion
in the applicable Qualified Products List whether or not such products have actually been so listed
by that date. The attention of the suppliers is called to this requirement, and the manufacturers
are urged to arrange to have the products that they proposed to offer to the Federal Government
tested for qualification in order that they may be eligible to be awarded contracts or orders for
the products covered by this specification. Information pertaining to qualification of products is
contained in paragraph 3.2 of this specification.
Notice. When Government drawings, specifications, or other data are used for any purpose other than
in connection with a definitely related Government procurement operation, the United States
Government thereby incurs no responsibility nor any obligation whatsoever; and the fact that the
Government may have formulated, furnished, or in any way supplied the said drawings,
specifications, or other data is not to be regarded by implication or otherwise as in any manner
licensing the holder or any other person or corporation or conveying any rights or permission to
manufacture, use, or sell any patented invention that may in any way be related thereto.
Custodian:
Preparing Activity:
Navy - Bureau of Yards and Docks Navy - Bureau of Yards and
Pocks
MILITARY SPECIFICATION PIPE AND PIPE FITTINGS,
GLASS FIBER REINFORCED PLASTIC
This amendment forms a part of Military Specification MIL-P-22245A(DOCKS), dated 12 March 1963.
PAGE 2
2.2 Under "American Society for Testing and Materials" change: "D1694-59T - Threads ...." to
"D1694-
67 - Standard Specification for Threads....".
3.1, Line 2. Delete "non-glass fiber".
PAGE 3
3.2, Last line. Change "Bureau of Yards and Docks" to "Naval Facilities Engineering Command". Make
similar changes throughout the specification.
3.2.2, Line 2. Change "Washington 25, D.C." to "Washington, D.C. 20390." PAGE 4
3.2.2(b), line 3. After "used" add "in the adhesive and in the fabrication of the pipe and
fittings".
Add new paragraph 3.2.6:
"3.2.6 Qualification certification. The manufacturer of products which have been listed on the
Qualified Products List shall, when requested by the Naval Facilities Engineering Command, submit
certification signed by a responsible official of management, attesting that the listed products
are still available from the listed plant, are being produced under the same conditions as
originally qualified, i.e., same process, materials, construction, design, manufacturer's part
number or designation and meet the requirements of the current issue of the specification. Failure
to provide the certification will be cause for removal from the Qualified Products List."
3.6. Delete paragraph.
PAGE 5
3.7.1. Delete second sentence and substitute: "The outside diameter (O.D.) of pipe made by
processes which provide a fixed 0.D. and an uncontrolled O.D. shall be in accordance with the
tolerance limits of Table I."
Table I. In heading of third column, before "O.D." add "Fixed". Table I. Add a fourth column
reading:
"Uncontrolled O.D. tolerance, Inches
±0.025
±.030
±.035
+.040
-.035
+.045
-.035
+.055
-.040
+.066
-.050
+.086
-.065
+.107
-.080
+.127
-.095
Add new paragraph:
"3.7.1.2 Wall thickness. Each length of pipe shall have a consistent wall thickness subject to the
O.D. tolerance limits of table I."
3.12, line 5. Delete "and fittings".
PAGES 6 and 7
3.23, line 1. Delete "and fittings".
PAGE 8
PAGE 9
4.3.2. After last sentence add "Unless the test method specifies otherwise, at least three samples
shall be tested."
4.3.2.1. Delete paragraph.
PAGE 13
4.4.1.1, Lines 1 and 2. Delete "produced in any one 24 hour period and to be" and after "delivery"
add "at the same time".
4.4.1.2, Line 2. Delete "produced in any one 24 hour period and to be" and after "delivery" add "at
the same time".
6.2. Delete sub-eleme
Regulation Sections
Section | Subject |
---|---|
§ 195.4 | Compatibility necessary for transportation of hazardous liquids or carbon dioxide |