Interpretation Response #00-0085 ([Safecraft Fire Protection Systems] [Mr. Donald E. Warren])
Below is the interpretation response detail and a list of regulations sections applicable to this response.
Interpretation Response Details
Response Publish Date:
Company Name: Safecraft Fire Protection Systems
Individual Name: Mr. Donald E. Warren
Location State: CA Country: US
View the Interpretation Document
Response text:
April 4, 2000
Mr. Donald E. Warren Ref. No. 00-0085
Vice President Engineering
Safecraft Fire Protection Systems
2708 Teagarden St.
San Leandro, CA 94577
Dear Mr. Warren:
This is in response to your letter dated March 22, 2000, regarding the applicability of the requirements contained in 49 CFR 173.309(a) of the Hazardous Materials Regulations (HMR; 49 CFR Parts 171-180) to your non-DOT specification fire extinguishers. Specifically, you request clarification on the requirements for the manufacture and transportation of small fire extinguishers containing liquefied compressed gases.
Your questions are paraphrased and answered as follows:
Q1. Is it true that a non-DOT specification cylinder that is used as a fire extinguisher and contains an extinguishing agent; such as Halon 1211 and Halon 1301, may have a volumetric capacity of no larger than 900 ml?
Al. The answer is yes. See §173.309 (a)(3)(i).
Q2. If a manufacturer states that a cylinder is "approved" by Underwriters Laboratories (UL/ULC), can it be assumed that it is a non-DOT specification cylinder and is subject to the 900 ml maximum capacity?
A2. The answer is yes, if the cylinder is not marked as conforming to an applicable specification; prescribed in part 178 of the HMR. A non-DOT specification cylinder used as a fire extinguisher must fully conform to the requirement prescribed in §173.3 09(a) and to the general packaging requirements prescribed in §173.24. The extinguishing agent must conform to the criteria in Special Provision 18 of §172.102.
Q3. Is it correct that a cylinder that is not marked or stamped with the applicable markings (i.e., DOT XX-XXX or DOT E-XXXX) would be classified as a non-DOT specification cylinder? Would this also include foreign-made cylinders, either unmarked/unidentified or with manufacturers information?
A3. The answer is yes. See A2 above.
Q4. If a fire extinguisher has an adhesive label that states, for example, "MEETS DOT REQUIREMENTS FOR ALUMINUM CYLINDERS", does this in anyway override the 900ml capacity limit?
A4. The answer is no. Because DOT has specifications for aluminum cylinders, this wording should not be used. The HMR require this particular notation to be marked on a cylinder: "MEETS DOT REQUIREMENTS"; See §173.309(a)(3)(iii).
Q5. Does §173.309 (a) provide for the use of a non-DOT specification cylinder with a capacity greater than 900 ml as a fire extinguisher if it will contain a liquefied compressed gas?
A5. The answer is no. However, you may submit an application for exemption in accordance with the procedures contained in §107.105. Your application must contain sufficient information to demonstrate that, if an exemption is issued, an equivalent level of safety will be achieved that is at least equal to that required by the regulations.
Q6. Under ' 173.309 (b), several DOT specification cylinders commonly used for fire extinguishers are absent from the list. For example, 4DS, 4D, welded steel cylinders which are used and shipped for aircraft fire protection, and DOT 39 cylinders which are commonly used for portable extinguishers. Is it correct that these cylinders are not limited to the 241 psig at 70 °F and 900 ml limitations as discussed above?
A6. The answer is yes. The quantity limitation prescribed in § 173.306(a) is applicable only to non-DOT specification cylinders. However, those cylinders referenced in your example are not authorized for shipment under §173.309. When filled with a liquefied compressed gas, the cylinders must be shipped in accordance with §173.304.
Q7. Are there any other requirements that specifically relate to the manufacture of non- DOT specification cylinders?
A7. DOT has no requirements on the manufacture of non-DOT specification cylinders used as fire extinguishers, other than as noted in §s173.24 and 173.309 (a). I suggest that you contact the National Fire Protection Association for any industry standards that may be applicable to fire extinguishers.
I hope this information is helpful.
Sincerely,
Hattie L. Mitchell, Chief
Regulatory Review and Reinvention
Office of Hazardous Materials Standards
173.309
Regulation Sections
| Section | Subject |
|---|---|
| 173.309 | Fire extinguishers |