USA Banner

Official US Government Icon

Official websites use .gov
A .gov website belongs to an official government organization in the United States.

Secure Site Icon

Secure .gov websites use HTTPS
A lock ( ) or https:// means you’ve safely connected to the .gov website. Share sensitive information only on official, secure websites.

U.S. Department of Transportation U.S. Department of Transportation Icon United States Department of Transportation United States Department of Transportation

Interpretation Response #PI-72-035 ([New Hampshire Public Utilities] [Bruce B. Ellsworth])

Below is the interpretation response detail and a list of regulations sections applicable to this response.

Interpretation Response Details

Response Publish Date:

Company Name: New Hampshire Public Utilities

Individual Name: Bruce B. Ellsworth

Location State: NH Country: US

View the Interpretation Document

Response text:

August 9, 1972

Mr. Bruce B. Ellsworth

Gas Safety Engineer

New Hampshire Public Utilities Commission

26 Pleasant Street

Concord, New Hampshire 03301

Dear Mr. Ellsworth:

This is in response to your letter dated July 26, 1972, and your telephone conversation with our Mr. Lance Heverly on August 2, 1972.

Your letter indicates that there is a situation in your State in which two parallel transmission lines, one of which is 6" and the other 10", are operating at approximately 400 psig. The transmission company intends to shut down the 6" line and make permanent field repairs to some corrosion leaks that had been repaired with leak clamps in 1968. From your conversation with Mr. Heverly, you agreed that the hoop stress of 7.15 percent of SMYS was in error, and that the pipe involved is Grade B,.188" wall thickness, and about 50 feet long. Your letter indicated that the company intends to X-ray all welds but questions whether a hydrostatic test is also required.

If the operating company plans to pressure test the replacing § Section of pipe in the operating pipeline, then the pressure test would have to be made with air or water since the permissible test pressure in a Class III location using gas, as set forth in § Section 192.503(c), falls just short of that required to comply with § Section 192.619(a)(2)(ii). However, gas, air, or water could be used on the fabricated short § Section of pipe at some other location than in the pipeline, such as covered by § Section 192.505 for pipe operating above 30 percent of SMYS, and then installed in the pipeline.

We trust that this has answered your particular question. If we can be of further service, please let us know.

Sincerely,

/signed/

Joseph C. Caldwell

Director

Office of Pipeline Safety