Interpretation Response #05-0266 ([Fire Protection Certification] [Mr. Edward O'Brien])
Below is the interpretation response detail and a list of regulations sections applicable to this response.
Interpretation Response Details
Response Publish Date:
Company Name: Fire Protection Certification
Individual Name: Mr. Edward O'Brien
Location State: MD Country: US
View the Interpretation Document
Response text:
Nov 21, 2005
Mr. Edward O'Brien Reference No. 05-0266
Fire Protection Certification
8719 Pete Wiles Road
Middletown, MD 21769
Dear Mr. O’Brien:
This responds to your letter concerning the cylinder requalification marking requirements under the Hazardous Materials Regulations (HMR; 49 CFR Parts 171-180). Specifically, you ask if a pressure sensitive label displaying the requalification markings may be placed on the sidewall of a composite (fiber wrapped) cylinder used as a fire extinguisher.
Section 180.213(c)(1) authorizes a cylinder used as a fire extinguisher to be marked by using a pressure sensitive label. It is permissible to place the label on the sidewall of a cylinder. Stamping the markings on the cylinder sidewall or any part of the fiber wrapped surface is prohibited.
I trust this satisfies your request.
Sincerely,
Hattie L. Mitchell
Chief, Regulatory Review and Reinvention
Office of Hazardous Materials Standards
180.213
Regulation Sections
Section | Subject |
---|---|
180.213 | Requalification markings |